What Is Battery Float Charge?

By Haijiang Lai

Owenr at SaftecEnergy

Table of Contents

If you leave a backup battery connected for months, you’ll hear the term float charge. It sounds technical, but the idea is simple: once a battery is already full, a charger holds it at a lower, gentle voltage so it won’t self-discharge. Float is common in telecom rooms and UPS systems. It’s helpful for lead-acid batteries, but it’s usually not needed (and can even be harmful) for lithium unless you set it carefully.

Below is a clear, step-by-step guide you can follow—even if you’ve never set a charger before.

What does “float charge” mean?

  • Definition: After the battery reaches full in the bulk and absorption stages, the charger drops to a lower, constant voltage called float.
  • Purpose: Offset natural self-discharge so the battery stays ready without overworking it.
  • Where it appears: UPS/telecom backup, emergency lighting, some solar/backup inverters.
  • Not the same as “keep charging to 100% all day.” Float should be lower than the charging voltage used to fill the battery.

Charging stages (in order): Bulk → Absorption → Float (Equalize exists for some flooded lead-acid only.)

How is float different from trickle, bulk, absorption and boost?

Stage/ModeWhat it doesTypical controlUse with lead-acid?Use with lithium (LiFePO4)?Main risk if misused
BulkFast filling from low SOCConstant current (rising voltage)None if limits are correct
AbsorptionFinish to 100%Constant voltage (current tapers)✅ (short)Over-time = heating/overcharge
FloatMaintain full, offset self-dischargeLower constant voltage✅ Standard for standby⚠️ Often disable; or set lowLong high-SOC dwell → aging (esp. lithium)
TrickleVery small current dripLow constant current⚠️ Easy to overdo❌ Not recommendedSlow overcharge on full battery
Boost/EqualizeHigher-than-normal voltage to rebalanceElevated voltage, limited time⚠️ Only for some flooded❌ NeverGas, water loss, damage

Plain English: Float = low voltage hold. Trickle = small current drip. They are not the same.

What float voltage is good for lead-acid?

Float must be lower than the absorption voltage and adjusted for temperature. The numbers below are typical ranges at 25 °C; always check your battery manual.

Flooded / AGM / Gel quick chart (25 °C)

SystemFlooded (V)AGM (V)Gel (V)
12 V13.5 – 13.813.4 – 13.613.2 – 13.5
24 V27.0 – 27.626.8 – 27.226.4 – 27.0
48 V54.0 – 55.253.6 – 54.452.8 – 54.0

Rules of thumb (25 °C):
Flooded ≈ 2.25–2.30 V/cell, AGM ≈ 2.23–2.27 V/cell, Gel ≈ ~2.20–2.25 V/cell.

How does temperature change float voltage?

Lead-acid wants lower voltage when it’s hotter and higher when it’s colder. A common slope is –3 mV/°C per cell from 25 °C.

  • Example, 12 V flooded (6 cells), set at 13.6 V at 25 °C:
    • At 35 °C (hot room): 13.6 V – (0.003 V × 10 °C × 6) ≈ 13.42 V
    • At 5 °C (cold room): 13.6 V + (0.003 V × 20 °C × 6) ≈ 13.96 V

Tip: Many chargers let you plug a temperature sensor onto the battery so the device adjusts automatically.

Should lithium (LiFePO4) be float charged?

Usually no. LiFePO4 doesn’t need long float because its self-discharge is very low, and staying at high state-of-charge (high voltage) for days can age the cells faster.

Better approach for LiFePO4

  • Disable float if your charger/inverter allows.
  • Use a “charge-to-full then stop” profile. Let the BMS terminate charging; only restart when the battery drops to a set SOC/voltage (e.g., restart at 40–60% SOC in off-grid solar).

If the menu requires a “Float” number for LFP

  • Enter a low standby value clearly below your absorption voltage.
  • Typical LFP examples (check your brand’s BMS guide):
    • 12 V LFP: Absorb 14.2–14.6 V; set “Float/Standby” around 13.4–13.6 V
    • 24 V LFP: Absorb 28.4–29.2 V; “Float/Standby” 26.8–27.2 V
    • 48 V LFP: Absorb 56.8–58.4 V; “Float/Standby” 53.6–54.4 V

The idea is not to hold lithium at 100% all day. Keep it ready, but avoid long high-voltage dwell.

When is float useful—and when can it hurt?

Useful

  • UPS/telecom standby (mostly lead-acid): systems must be instantly ready; float keeps them topped without full-power charging.
  • Emergency lighting and alarms with lead-acid.

Can hurt

  • High temperature + high float voltage: speeds up water loss and dry-out (flooded/AGM/gel).
  • Lithium kept at high SOC: accelerates side reactions and capacity fade.
  • Small chargers mis-set as trickle: a tiny current for months can still overcharge.

Best practices

  • Use the right float range for your chemistry.
  • Enable temperature compensation and mount the probe on a battery case, away from heat sources.
  • Provide ventilation for lead-acid rooms.
  • For lithium off-grid, prefer float disabled with smart restart thresholds.

How do you set float in solar controllers and UPS menus?

  1. Find the menu: In MPPT/hybrid inverters look for Bulk/Absorb/Float/Equalize. In UPS, look under Battery settings → Float/Standby.
  2. Enter values:
    • Lead-acid → use the table above; add temperature compensation.
    • LiFePO4 → disable float or set low standby; reduce absorb time.
  3. Set re-bulk / re-charge: Don’t restart charging for tiny drops. For lithium, many users choose a lower restart SOC (e.g., 50%).
  4. Save and test: Watch the actual terminal voltage with a meter for 10–15 minutes to confirm.

Five mistakes to avoid

  1. Keeping lithium at a lead-acid float value all day.
  2. No temperature probe on lead-acid—hot rooms need lower float.
  3. Absorption time too long → battery stays hot and gassy.
  4. Long trickle on a battery that is already full.
  5. Measuring at the charger only—cable drop can hide an over-float at the battery.

Does float charging damage a battery if it stays connected?

  • Lead-acid: Safe when voltage and temperature compensation are correct. Check electrolyte (flooded), and keep the room cool.
  • Lithium (LFP): Long high-SOC can shorten life. Use disable/low-standby strategies instead.

Warning signs

  • Battery case feels warm at rest
  • Noticeable smell (lead-acid gassing)
  • Capacity seems to drop month by month

How do you check float voltage safely?

  1. Tools: Digital multimeter (DMM), insulated probes, eye protection.
  2. Where to measure: Measure directly at the battery terminals. Don’t rely on the charger display alone.
  3. When to measure: After the system has been in Float for 5–10 minutes with normal loads.
  4. What to record: Voltage, battery temperature, room temperature.
  5. Adjust: If numbers don’t match your target (table above), tweak the menu and retest.

What real-world examples make this clear?

  • Hot UPS room (32 °C) with 2.30 V/cell: Water loss and early failure. After enabling –3 mV/°C/cell compensation, float drops ~0.18 V on a 12 V block and lifespan improves.
  • Off-grid solar with LFP: Float disabled. Absorb ends at 14.4 V, then the inverter powers loads; re-charge only when SOC drops to 50%. Result: fewer high-SOC hours, longer life.
  • RV flooded battery on maintainer: Float 13.6 V at 25 °C; once a month check electrolyte and, if the maker recommends, run a brief equalize to desulfate (flooded only).

Float Charge Faq

What is a safe float voltage for a 12 V AGM?
Around 13.4–13.6 V at 25 °C, with temperature compensation.

Is float charging the same as trickle?
No. Float controls voltage at a low level; trickle feeds a small current. Float is safer for standby.

Can float revive a sulfated lead-acid?
No. Sulfation needs proper equalize (flooded only) or a dedicated reconditioning method—follow the battery maker’s instructions.

Does float charging damage lithium batteries?
Long high-SOC can speed aging. Prefer disable float or set a low standby value and use restart thresholds.

What is the 80/20 rule—does it apply here?
That rule is a charging habit (charge at 20%, stop at 80%). It’s not a float setting. Float is for standby after full.

How do I set float for 24 V and 48 V lead-acid?
Double or quadruple the 12 V values respectively (see the table).

Where should I place the temperature probe?
On a battery case in the middle of the bank, away from hot air or heatsinks.

How often should I equalize?
Only for flooded batteries and only as the manufacturer recommends. AGM/Gel/Lithium: do not equalize.

Why does my charger show float but the battery reads higher?
Cable drop or wrong sensing point. Measure at the terminals and enable remote sense if available.

Can I leave a maintainer on my car all winter?
Yes for lead-acid if the maintainer is smart and follows proper float ranges. For lithium car retrofits: follow the pack maker’s guidance.

Download: float quick chart and a simple calculator

Want an easy worksheet? Ask us for a PDF quick chart (lead-acid float vs temperature) and a one-cell mV/°C calculator you can keep on your phone.

Need help setting a charger?
We configure batteries and inverters every day. If you’re moving to LiFePO4 home storage, we’ll share a float-free profile that protects cycle life while keeping your lights on.

As a supplier of energy storage products, my purpose in discussing this topic is to share with you how batteries are shaping different industries. If you are planning a project that requires Rack Battery, Lifepo4 Battery, or Home Storage Battery, contact us today to get a tailored solution.

Saftec Energy is dedicated to providing reliable and future-focused energy solutions. Our mission is to support households and businesses with safe, efficient, and sustainable power systems.
We continue to grow with innovation and responsibility, helping our partners achieve stability in an energy-dependent world. 📧 Mail: saftecenergy@gmail.com

Welcome to SaftecEnergy!

Need energy you can count on? Saftec Energy is ready to help—whether it’s for home, business, or solar projects. Let’s power your ideas together.

Follow me:

Start Your Energy Plan Now

📧→ saftecenergy@gmail.com